TOPIC: Is this an S-trap?

Is this an S-trap? 12 years 4 days ago #50868

  • elpeacen
  • elpeacen's Avatar Topic Author
  • Visitor
  • Visitor
I just inspected this house, and I am concerned that, in one of the bathrooms, there was a drop in the waste piping six inches after the p-trap. Is that too close? Would that make this the same danger as an s-trap? I could certainly use an answer before I finish this report!!
Attachments:

Please Log in to join the conversation.

Re: Is this an S-trap? 12 years 4 days ago #50876

Yes

Please Log in to join the conversation.

Home Inspector
HVAC Systems Design
ITC Level III Thermography - Building Science Thermographer
Thermal Imaging
Serving Clarksville - Nashville TN and the Mid TN area
www.MidTnInspections.com
www.ThermalImagingScan.com
To link to my pages:
www.midtninspections.com/link-submission

Re: Is this an S-trap? 12 years 4 days ago #50885

It is based on the horiztonal run. ? It has to be at least 2x long as the pipe diameter.

So if you have 1.25 pipe, it has to have a horizontal run of at least 2.5 inches before it turns down. ? Looks like you don't have the required horizontal run. ? ]