I did an inspection on a new construction the other day and I wanted to know what the height requirements are for a natural gas fireplace. I measured the horizontal clearance at 7 feet from chimney to roof. I know that wood burning fireplaces should have a 10 foot horizontal clearance. Is the 10 foot horizontal clearance rule the same for natural gas burning fireplaces?
I called it out as needing to be raised to the 10 foot horizontal clearance. Thanks in advance!!! |
Please Log in to join the conversation.
HLC Home Inspections LLC
www.OklahomaHomeInspector.biz We are a licensed inspector for the state of Oklahoma.? Our focus is Oklahoma City, Moore, Mustang, Yukon, Tuttle, and many other areas surrounding OKC. HLC-Home-Inspections-Oklahoma-City HLC Home Inspections LLC... |
|
Looks like it's still 10 feet from the spot 2 feet below the roof. Source:
www.inspect-ny.com/chimneys/Chimney_Height.htm
|
Please Log in to join the conversation.
Dominic Maricic
Home Inspector Pro Home Inspection Software - CEO |
|
Sweet thanks Dom. I couldn't find anything that specifically addressed my question until now. Everything I was finding addresses it as a wood burning fireplace first. Karma for you kind Sir.
|