Alright boys, here is a fresh pic from a home inspection today. This is the side of a gas pack up in the attic. You tell me what you think. I told the lady she needs to have it serviced and looked over, before she buys!
|
Please Log in to join the conversation.
Knoxville TN Home Inspector
Fogarty Home Inspection Services Professional mold and radon testing of east Tn Professional home and commercial inspections of Knoxville www.homeinspectorknoxville.com Title: Home Inspector Knoxville Meta Keywords- Knoxville home inspection, Oak Ridge TN home inspector,... |
|
That appears to be combustion gas or heated air leaking out and condensing on the wall surface causing the rust. I can't tell the orientation of the unit from the pics, but that is my opinion of what is happening.
|
Please Log in to join the conversation.
<b>Title:</b>
Orland Park Home Inspector
www.OrlandParkHomeInspections.com <b>Des:</b> Orland Park Home inspector performs home inspections in Orland Park, Tinley Park, New Lenox, Frankfort, & Palos Heights. 708-535-6057, 708-612-6679 <b>UPath:</b>...
Last Edit: by Michael Merino.
|
|
Without seeing the whole view of furnace or what that section is it is hard to tell. Not sure where the exhaust vent is but moisture can cause a lot of damage. Yes refer out to be further inspected.
|
Please Log in to join the conversation.
Bent Nail Inspections
Serving Boise, Meridian, Eagle, Nampa, Caldwell and surrounding areas Boise home inspector, boise home inspections, Meridian home inspector, Idaho Home Inspection, Nampa Home Inspector Boise home Inspections www.bestboisehomeinspection.com/ ...
Last Edit: by Davin Strand.
|
|
This absolutely should have been called out as you say you did! It is evident that the system is rusting out, which does reek of a moisture problem! But even more important, if this is a combustible system, the weakening of the walls will probably eventually lead to carbon monoxide issues as well; and with this system being in the attic, where many people are going to forget that it is even there, there is a dangerous possibility of unawareness when holes in the system begin to form. Recommending further evaluation was the Right On thing to do!
|
Please Log in to join the conversation.
Ed DeRousse
Best Choice Home Inspection's www.northernvirginiahomeinspector4u.com Home Inspector Providing Home Inspections and Radon Testing in Alexandria, Fairfax, Manassas, Stafford, Woodbridge and anywhere in the Leesburg or Northern Virginia area's. |
|
Condensation is common in those units in attic spaces.
What are they doing with one of those metal shower stalls in the attic?? |
Please Log in to join the conversation.
Jay Markanich Real Estate Inspections, LLC
Based in Bristow, serving all of Northern Virginia www.jaymarinspect.com Northern Virginia Home Inspector Festina Lente - Make Haste Slowly |
|
Yes, condensation is common when the system is found in the attic, and as we plainly see, breakdown does develop because of it.
It's not clearly visible Jay, but in the lower photo, I believe that I can make out a water heater that appears to be sitting in the pan. |