TOPIC: Electrical Panel Wire Gauge Difference

Electrical Panel Wire Gauge Difference 15 years 9 months ago #6982

  • Scott Widick
  • Scott Widick's Avatar Topic Author
  • Offline
  • Premium Member
  • Premium Member
  • Now thats thinkin with your dipstick Jimmy!
  • Posts: 143
  • Thank you received: 0
Hello Hippies,

I have another defect for discussion.  I noticed 2 strands of heavy gauge (2) spliced into 12 gauge at the main panel. What do you say? I have attached a pic for your pleasure.
Attachments:

Please Log in to join the conversation.

SPACE EXPLORATIONS, LLC
www.sehomeinspection.com
Monument, Castle Rock, Lone Tree, Pueblo,Clorado Springs
Last Edit: by Scott Widick.

Re: Electrical Panel Wire Gauge Difference 15 years 9 months ago #6986

Scott, any other pics of that panel?

Please Log in to join the conversation.

South Sound Inspections
Performing Home Inspections in the Seattle, Olympia and Bremerton areas.

www.washingtonhomeinspector.biz

Re: Electrical Panel Wire Gauge Difference 15 years 9 months ago #6987

  • Scott Widick
  • Scott Widick's Avatar Topic Author
  • Offline
  • Premium Member
  • Premium Member
  • Now thats thinkin with your dipstick Jimmy!
  • Posts: 143
  • Thank you received: 0
Yes, See original post

Please Log in to join the conversation.

SPACE EXPLORATIONS, LLC
www.sehomeinspection.com
Monument, Castle Rock, Lone Tree, Pueblo,Clorado Springs

Re: Electrical Panel Wire Gauge Difference 15 years 9 months ago #6991

Scott,
I can't really tell by the pics.  Was there an A/C unit, maybe a 220v, possibly a microwave feed installed?  Were you able to trace it beyond the service panel? Either way, if it is a "jump" then it is not correct.  I see the panel is full and very well could be a home owner "addition".

Please Log in to join the conversation.

South Sound Inspections
Performing Home Inspections in the Seattle, Olympia and Bremerton areas.

www.washingtonhomeinspector.biz

Re: Electrical Panel Wire Gauge Difference 15 years 9 months ago #7011

Scott - same good.  Different not good.  Splice not professional.  Homeowner job...  At least he used electricial tape!  I'm a bit surprised it isn't duct tape.

The dust getting into that box is also a problem - disconnected dryer vent nearby?

The missing breaker at the bottom is also a problem - was something removed to accommodate that interesting splice?

Please Log in to join the conversation.

Jay Markanich Real Estate Inspections, LLC
Based in Bristow, serving all of Northern Virginia
www.jaymarinspect.com
Northern Virginia Home Inspector
Festina Lente - Make Haste Slowly

Re: Electrical Panel Wire Gauge Difference 15 years 9 months ago #7041

Thanks Scott:
First the splice is not code.  A splice in the panel is Ok providing only one wire goes to the breaker and both wires are the same gauge.
Their can be no empty spaces in the breaker  panel.

Please Log in to join the conversation.