• 888-750-4777
  • This email address is being protected from spambots. You need JavaScript enabled to view it.
Welcome, Guest
Username: Password: Remember me

TOPIC: Double tapped 15 and 20 amp breakers-

Double tapped 15 and 20 amp breakers- 12 years 5 months ago #49074

If you have no other electrical issues but you find one double tapped 15 or 20 amp breaker do you recommend an electrician (call it out as a defect)?

Please Log in to join the conversation.

Jesus is coming again!!

Re: Double tapped 15 and 20 amp breakers- 12 years 5 months ago #49083

Depends,

Is it the low voltage transformer? Some call this out some do not.

Yes a double tap is a defective condition and needs to be addressed by a qualified electrician.

Verbiage:
(Double tapping), two or more wires on a single pole breaker can add to the load of the affected circuit causing a possible overload and tripping breakers, or result in loose connections and overheating of the breaker or connections.

Or
DOUBLE TAPmultiple conductors listed for single conductors noted at breaker(s). Recommend a qualified professional review the panel manufacturers instructions for proper attachment.

Please Log in to join the conversation.

Home Safe Home Inspections
Link Url: Cleveland Home Inspector - www.hshinspections.net/
Body:Performing Home Inspections in Cleveland, Parma, Brecksville, Broadview Heights, North Royalton, Strongsville and surrounding areas.
Keywords:Parma,Broadview...
Last Edit: by David Macy.

Re: Double tapped 15 and 20 amp breakers- 12 years 5 months ago #49084

Thank you David!

Please Log in to join the conversation.

Jesus is coming again!!

Re: Double tapped 15 and 20 amp breakers- 12 years 5 months ago #49096

Dumb question but are you sure it was a double tap?  Brand of breaker / panel?  Sometimes it is hard to see the connection point on the breaker.  Double taps are easy repairs in most circumstances with a pigtail.  In my state, since it is a licensed trade, I am required to recommend a licensed electrician.

Please Log in to join the conversation.

There is nothing sweeter than the smell of fresh cut grass on a baseball infield, the click of a wooden bat and the taste of a hot dog at a warm sunny daytime double-header.

Re: Double tapped 15 and 20 amp breakers- 12 years 5 months ago #49100

My sister in Richmond, Va complained that an inspector cited her double tapped breaker. The buyer wanted an electrician, and the electrician told my sister it was a Sq D panel and had a breaker specifically designed for double tapping. I've been looking into it since, and looking for it on my inspections. Maybe the type of breaker is designed for double tapping but care should be taken that it doesn't cause an overload? Any time I see double tapping, or any wiring issue, I always recommend an electrician make the repairs. We don't know the client's or homeowner's capabilities. I always assume my client is 96 yrs old and legally blind, so she can't repair anything!

Please Log in to join the conversation.

Always tell the truth, do what you promise, and do it righter than right..always
Title: Inspection Connection
URL: www.charleston-home-inspector.com
Body: Performing Home Inspections in all of WV: Charleston, Huntington, Teays, Hurricane, and surrounding areas
Keywords: Charleston Home Inspector, St...

Re: Double tapped 15 and 20 amp breakers- 12 years 5 months ago #49101

Sq. D breakers generally allow double tapping per the manufacturer's instructions.  Thus, if such a connection is made it poses no hazard but may result in the breaker tripping if the combined load exceeds the breaker's rating.  Just like any other circuit, a tripping breaker is due to an overloaded or faulted circuit, but that is a different problem than whether the breaker has one or two wires connected to it.  With respect to low voltage transformers in the panel (mentioned above) I always write that as a defect.

Please Log in to join the conversation.

Title : Emerald City Inspections, LLC- Dublin, GA
URL : www.dublinhomeinspections.com
Desc: Emerald City Inspections, LLC performs guaranteed "peace of mind" property inspections in Dublin and Laurens County, Georgia.  Call today - your home inspector for life !
Meta Keys : Certified...
Time to create page: 0.212 seconds
© 2004-2024 Home Inspector Pro Inc. All Rights Reserved.