I did a recent inspection with a Hot tub and everything about the circuit was wrong.
I wanted to ask/discuss my findings and if there are any other issues/requirements for the circuit. My findings. No disconnect within 6 feet of Tub. No GFCI protection. Cable improperly secured, installed at main panel, sub floor and exterior. BX cable used at exterior and noted as a trip hazard and not rated for exterior usage. Here are a few pics and just wanted to know for next time if anything else to document. |
Please Log in to join the conversation.
Home Safe Home Inspections
Link Url: Cleveland Home Inspector - www.hshinspections.net/ Body:Performing Home Inspections in Cleveland, Parma, Brecksville, Broadview Heights, North Royalton, Strongsville and surrounding areas. Keywords:Parma,Broadview... |
|
I think you covered it, unless those conductors are entering some duct work in the 2nd photo.
Looks like an amateur install all the way around. |