The connections don't look right to me. All the wiring is under the screws of the breakers but it looks like they should be inserted between two plates and the screw tightening down on it. I think that the picture shows that some of the wiring is only barely under the screw. The metal plates may not be visible though. The panel was a Commander.
Thanks |
Please Log in to join the conversation.
Bert de Haan
www.KitchenerWaterlooHomeInspector.ca Benchmark Home Inspection Services Kitchener-Wateroo and Guelph area Home Inspection Serving Kitchener-Waterloo, Guelph, Orangeville, Mount Forest and surrounding areas. Keywords: Kitchener-Waterloo home inspector, Guelph home inspection,... |
|
Bert,
I just saw this thread, and am surprised nobody has chimed in. You probably already have your answer from another source, but, here's mine anyway. You are exactly correct. The conductor should be between the two cinch plates. Never directly under the screw (or next to it) for this style breaker. This is a giveaway of a Harry Homeowner install, or a really "wet-behind-the-ears" sparky wanna-be. |
Please Log in to join the conversation.
Jeffrey R. Jonas
507.213.7468 This email address is being protected from spambots. You need JavaScript enabled to view it. FB: www.facebook.com/MN.Home.Inspector www.JRJConsultants.net www.OwatonnaHomeInspector.com www.MinnesotaCommercialBuildingInspections.com URL: www.owatonnahomeinspector.com Title: Critical Eye Property Inspections Description: Providing... |
|
As you may have guessed, I completed the report (and wrote this up) but thanks just the same for your comment.
|