Hello all,
Inspected a home this morning. ? The water heater flue came off of the vent hood and immediately went to a elbow. ? I know this isn't ideal but is it forbidden. ? If so do you have any info on it. ? This is all I could find. ? There should be a rise of ten vent diameters off of the top of the heater before the first elbow. On a heater that has a three inch vent that would be 30 inches before an elbow. ? |
Please Log in to join the conversation.
Jesus is coming again!!
|
|
The bend is not the issue, its the rise in the vent thats important. The vent should rise 1/4 inch per linear foot. Here is a link that might be useful.
www.checkthishouse.com/49/water-heater-v...ater_vent_pipe_pitch |
Please Log in to join the conversation.
Tech 9 Home Inspections
|
|
Great link, thanks Jarrod!
|
Please Log in to join the conversation.
Dominic Maricic
Home Inspector Pro Home Inspection Software - CEO |
|
Mike... The alledged "ten vent diameters" rule would be impossible in most basements in MN. With an average height of a 30-40 gal WH at approx. 66 inches, adding the 30 inches... for 96 inches total before the first elbow! That just isn't ever going to happen!
|
Please Log in to join the conversation.
Jeffrey R. Jonas
507.213.7468 This email address is being protected from spambots. You need JavaScript enabled to view it. FB: www.facebook.com/MN.Home.Inspector www.JRJConsultants.net www.OwatonnaHomeInspector.com www.MinnesotaCommercialBuildingInspections.com URL: www.owatonnahomeinspector.com Title: Critical Eye Property Inspections Description: Providing... |