Did an inspection today where I couldn't find a relief valve on the electric water. The water heater was from 1997. I couldn't even find a place where it should have been. There is a temperature limiting device behind one of the access doors. Possibly a pressure relief valve could be installed somewhere down the line I guess but I didn't see one. I looked up a schematic of the model. It did have a TPR. It was different in other ways as well so that may not be that reliable. I am planning to call the manufacturer (GSW) but first wanted to ask you guys.
|
Please Log in to join the conversation.
Bert de Haan
www.KitchenerWaterlooHomeInspector.ca Benchmark Home Inspection Services Kitchener-Wateroo and Guelph area Home Inspection Serving Kitchener-Waterloo, Guelph, Orangeville, Mount Forest and surrounding areas. Keywords: Kitchener-Waterloo home inspector, Guelph home inspection,...
Last Edit: by Bert de Haan.
|
|
Thinking about it a bit more, with a temperature limiting device behind the access panel, there wouldn't necessarily be the regular location for a pressure relief. It could be in the line as long as it is between the tank and a shutoff valve. It wasn't there. Plumber messed up.
|
Please Log in to join the conversation.
Bert de Haan
www.KitchenerWaterlooHomeInspector.ca Benchmark Home Inspection Services Kitchener-Wateroo and Guelph area Home Inspection Serving Kitchener-Waterloo, Guelph, Orangeville, Mount Forest and surrounding areas. Keywords: Kitchener-Waterloo home inspector, Guelph home inspection,... |
|
Many heaters come with them pre-installed. They are very expensive, maybe $10 so he was saving money or stole it to put on his own heater. ;-( |
Please Log in to join the conversation.
True Professionals, Inc. Home inspections and Property Consultation, Litigation Support, HOA Maintenance Consulting
www.HomeInspection-LosAngeles.com Certified Infrared Thermographer www.MagicLeakFinders.com www.Thermal-Diagnostics.com All services provided in the Southern... |
|
All water heaters are required to have a TPR valve installed. The location of the TPR should be within 6 inches from the top of the water heater in order to have the probe in the hottest environment to sense the temperature and operate at 210 degrees F. This is here to protect the water heater from over pressurizing and to protect the occupants from having steam coming out of the faucets. Remote water temperature regulators can fail so you need the TPR there for protection.
|
Please Log in to join the conversation.
Tristar Consultants
URL: www.tristarconsultants.net Tristar Consultants Home Inspection, providing home inspection services for home buyers, sellers and investors, in Buffalo, Erie County, Niagara County and all of Western New York. Buffalo Home Inspector. Swimming Pool and Spa Inspection, Certified... |
|
Most water heaters are not "planted" in bathrooms. There are most commonly installed in attics, crawlspaces, garages, basements, and utility closets in the US of A. Most electric water heaters are not "plugged" in but are rather hardwired to a dedicated circuit. If a water heater explodes, it will damage the house but not likley to damage the "entire house electricity". I recommend you check your facts before posting again.
|
Please Log in to join the conversation.
Bruce Ramsey, ACI
|
|
This is obviously not an English as the primary language poster or a machine translation.
Not sure what this is about. Obviously confused and non-valid information. Maybe they "grow" their water heaters where she's from and so have to plant them where needed? I suppose if the W/H did blow up, it would damage the electrical system as well as the house no doubt. Very "organic" I'd say. |
Please Log in to join the conversation.
True Professionals, Inc. Home inspections and Property Consultation, Litigation Support, HOA Maintenance Consulting
www.HomeInspection-LosAngeles.com Certified Infrared Thermographer www.MagicLeakFinders.com www.Thermal-Diagnostics.com All services provided in the Southern... |
|
|