• 888-750-4777
  • This email address is being protected from spambots. You need JavaScript enabled to view it.
Welcome, Guest
Username: Password: Remember me
  • Page:
  • 1
  • 2

TOPIC: HVAC and breakers

Re: HVAC and breakers 13 years 4 months ago #43037

Agree with Jim. 30 AMP is preferred for this application (125% = 31.25 AMP's). If a 25 AMP was used, the breaker would trip often, due to the sartup spike of the electrical motor.

Please Log in to join the conversation.

Jeffrey R. Jonas
507.213.7468
This email address is being protected from spambots. You need JavaScript enabled to view it.

FB: www.facebook.com/MN.Home.Inspector

www.JRJConsultants.net
www.OwatonnaHomeInspector.com
www.MinnesotaCommercialBuildingInspections.com

URL: www.owatonnahomeinspector.com
Title: Critical Eye Property Inspections
Description: Providing...
  • Page:
  • 1
  • 2
Time to create page: 0.202 seconds
© 2004-2024 Home Inspector Pro Inc. All Rights Reserved.