• 888-750-4777
  • This email address is being protected from spambots. You need JavaScript enabled to view it.
Welcome, Guest
Username: Password: Remember me

TOPIC: TPR valves

Re: TPR valves 14 years 3 months ago #34880

  • Bert de Haan
  • Bert de Haan's Avatar
  • Offline
  • Platinum Member
  • Platinum Member
  • If it is worth doing, it's worth doing well.
  • Posts: 741
  • Thank you received: 0

Watts 210 valves AND an exterior installed pressure relief valve are acceptable alternatives (check your area AHJ) to a TPR valves that would have their discharge lines terminate on the interior of a home.

Interior land-locked WH's are really difficult to have a properly terminated discharge line. As I've witnessed a lot of water damage from a leaking TPR valve, I'll recommend an installation of a 210, but would check in your own area.

Just a thought

That doesn't address electric water heaters.  Water damage is miserable but not as miserable as an exploding tank. 

Please Log in to join the conversation.

Bert de Haan
www.KitchenerWaterlooHomeInspector.ca
Benchmark Home Inspection Services Kitchener-Wateroo and Guelph area Home Inspection
Serving Kitchener-Waterloo, Guelph, Orangeville, Mount Forest and surrounding areas.
Keywords: Kitchener-Waterloo home inspector, Guelph home inspection,...

Re: TPR valves 14 years 3 months ago #35069

When water heaters are installed above or within habitable space they are required to be in a pan not less than 1-1/2" deep and shall have a pan drain. The pan drain shall extend full size to a suitably located indirect waste receptor or shall extend to the exterior of the building and terminate not less than 6" and not more than 24" above the adjacent ground surface

Please Log in to join the conversation.

Mark Tyson
Tyson Home Inspections
NACHI 109061301
Certified General Contractor cgc1516843
www.TysonHomeInspections.com

Re: TPR valves 14 years 3 months ago #35110

Watts 210 valves AND an exterior installed pressure relief valve are acceptable alternatives (check your area AHJ) to a TPR valves that would have their discharge lines terminate on the interior of a home.

Interior land-locked WH's are really difficult to have a properly terminated discharge line. As I've witnessed a lot of water damage from a leaking TPR valve, I'll recommend an installation of a 210, but would check in your own area.

Just a thought

That doesn't address electric water heaters.  Water damage is miserable but not as miserable as an exploding tank. 


I wonder why Watts has not created a Watts 210 for Electric?>

Please Log in to join the conversation.

Time to create page: 0.192 seconds
© 2004-2024 Home Inspector Pro Inc. All Rights Reserved.