• 888-750-4777
  • This email address is being protected from spambots. You need JavaScript enabled to view it.
Welcome, Guest
Username: Password: Remember me

TOPIC: Panel Question

Panel Question 15 years 1 month ago #22314

Yesterday I saw a double tapped 15A breaker, with the double running out of the box to the door bell transformer.  I'm calling it out on the basis of the double tap.  Thoughts?
Also, main panel is rated 125A, main disconnect is a double handled 100A, but the SE wiring is 2 AWG aluminum, rated at 100A.  I'm calling that as 100A service, but with the problem of a 200A main disconnect (too large a breaker, won't trip).  Just looking for a little feedback.
Off the the Twins game this afternoon; kids should have fun!  :)

Please Log in to join the conversation.

Title: Root River Inspections
URL:  www.arochestermnhomeinspector.com
Body:  Root River Inspections serves Rochester, Winona, Red Wing, Austin, Albert Lea and surrounding Minnesota areas.
Meta Key:  Rochester home inspector, Winona home inspector, Red Wing home inspector, Albert...

Re: Panel Question 15 years 1 month ago #22326

Have fun at the game ;)

Please Log in to join the conversation.

Dominic Maricic
Home Inspector Pro Home Inspection Software - CEO

Re: Panel Question 15 years 1 month ago #22329

Do you have pics of the main disconnect?  I could be misunderstanding you, but it sounds like your describing a 100A main disconnect and calling it incorrectly as a 200 A disconnect.

Please Log in to join the conversation.

HLC Home Inspections LLC
www.OklahomaHomeInspector.biz
We are a licensed inspector for the state of Oklahoma.?  Our focus is Oklahoma City, Moore, Mustang, Yukon, Tuttle, and many other areas surrounding OKC.
HLC-Home-Inspections-Oklahoma-City

HLC Home Inspections LLC...

Re: Panel Question 15 years 1 month ago #22331

Here's a pic of the panel.  You can see the main disconnect at the upper left of the breakers.  Did I goof and call it out incorrectly?  I haven't sent the report yet (client requested that I not cash his check till Tues.  Uh huh... ::)  )
Attachments:

Please Log in to join the conversation.

Title: Root River Inspections
URL:  www.arochestermnhomeinspector.com
Body:  Root River Inspections serves Rochester, Winona, Red Wing, Austin, Albert Lea and surrounding Minnesota areas.
Meta Key:  Rochester home inspector, Winona home inspector, Red Wing home inspector, Albert...

Re: Panel Question 15 years 1 month ago #22334

If the SE cables are 2 AWG aluminum then that is what you use to determine the Amps. The AWG, panel and breaker should all match, but if they don't then SE cable is the default. The breakers in this panel are 100 amp the SE cable is 100 amp. The breakers are 100 amp per leg, you do not add them together. The panel is rated higher than 100 Amp, so I think it is OK.

The double tap is a good call unless the breaker is made to accept a double tap.

Please Log in to join the conversation.

<b>Title:</b> Orland Park Home Inspector
www.OrlandParkHomeInspections.com
<b>Des:</b> Orland Park Home inspector performs home inspections in Orland Park, Tinley Park, New Lenox, Frankfort, & Palos Heights. 708-535-6057, 708-612-6679
<b>UPath:</b>...
Last Edit: by Michael Merino.

Re: Panel Question 15 years 1 month ago #22335

I wouldn't' release the report until the check clears.

Please Log in to join the conversation.

<b>Title:</b> Orland Park Home Inspector
www.OrlandParkHomeInspections.com
<b>Des:</b> Orland Park Home inspector performs home inspections in Orland Park, Tinley Park, New Lenox, Frankfort, & Palos Heights. 708-535-6057, 708-612-6679
<b>UPath:</b>...
Time to create page: 0.211 seconds
© 2004-2024 Home Inspector Pro Inc. All Rights Reserved.