• 888-750-4777
  • This email address is being protected from spambots. You need JavaScript enabled to view it.
Welcome, Guest
Username: Password: Remember me
  • Page:
  • 1
  • 2

TOPIC: Bonding and Grounding

Bonding and Grounding 15 years 4 months ago #17132

  • Joe Tedesco
  • Joe Tedesco's Avatar Topic Author
  • Offline
  • Senior Member
  • Senior Member
  • IAEI Certified Electrical Inspector since 1979
  • Posts: 58
  • Thank you received: 0
Basic Question:

Why is bonding the neutral to the EGC beyond the service equipment a bad idea?

Please Log in to join the conversation.

Joe Tedesco, NEC® Consultant

Re: Bonding and Grounding 15 years 4 months ago #17134

  • James Levy
  • James Levy's Avatar
  • Offline
  • Platinum Member
  • Platinum Member
  • NJ#24GI00101400, FL # HI7765
  • Posts: 872
  • Thank you received: 0
The possibility of energizing the electrical equipment and associated (attached) metal components exists from stray or unwanted neutral currents exists.

Please Log in to join the conversation.

www.homespectllc.com
Homespect LLC
Home and commercial Inspections in Medford, Mount Laurel, Cherry Hill, Voorhees, Marlton NJ, and the surrounding areas.

Re: Bonding and Grounding 15 years 4 months ago #17166

Sounds like a good answer to me.

Please Log in to join the conversation.

HLC Home Inspections LLC
www.OklahomaHomeInspector.biz
We are a licensed inspector for the state of Oklahoma.?  Our focus is Oklahoma City, Moore, Mustang, Yukon, Tuttle, and many other areas surrounding OKC.
HLC-Home-Inspections-Oklahoma-City

HLC Home Inspections LLC...

Re: Bonding and Grounding 15 years 3 months ago #17517

  • James Levy
  • James Levy's Avatar
  • Offline
  • Platinum Member
  • Platinum Member
  • NJ#24GI00101400, FL # HI7765
  • Posts: 872
  • Thank you received: 0
I guess we'll never know if it is right or not. :-\ I think it is.

Please Log in to join the conversation.

www.homespectllc.com
Homespect LLC
Home and commercial Inspections in Medford, Mount Laurel, Cherry Hill, Voorhees, Marlton NJ, and the surrounding areas.

Re: Bonding and Grounding 15 years 3 months ago #17537

Give Joe some time to answer. He's involved in a big project right now. He called me a few days ago.

Please Log in to join the conversation.

Dominic Maricic
Home Inspector Pro Home Inspection Software - CEO

Re: Bonding and Grounding 15 years 3 months ago #17551

  • Joe Tedesco
  • Joe Tedesco's Avatar Topic Author
  • Offline
  • Senior Member
  • Senior Member
  • IAEI Certified Electrical Inspector since 1979
  • Posts: 58
  • Thank you received: 0
Please forgive the delay, sometimes I am unable to gain access to the internet because of the weather, but now I can.  :)

I was happy with your reply, it provides a good answer in the form of a one liner that can be further researched by reviewing the NEC or NECH in Section 408.40

Please Log in to join the conversation.

Joe Tedesco, NEC® Consultant
  • Page:
  • 1
  • 2
Time to create page: 0.241 seconds
© 2004-2024 Home Inspector Pro Inc. All Rights Reserved.